| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| An Incorrect Default Permissions issue was discovered in Schneider Electric Wonderware InduSoft Web Studio v8.0 Patch 3 and prior versions. Upon installation, Wonderware InduSoft Web Studio creates a new directory and two files, which are placed in the system's path and can be manipulated by non-administrators. This could allow an authenticated user to escalate his or her privileges. |
| An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker may be able to disrupt a targeted web server, resulting in a denial of service because of UNCONTROLLED RESOURCE CONSUMPTION. |
| Schneider Electric StruxureWare Data Center Expert before 7.4.0 uses cleartext RAM storage for passwords, which might allow remote attackers to obtain sensitive information via unspecified vectors. |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes. |
| A vulnerability exists in Schneider Electric's Pro-Face GP Pro EX version 4.07.000 that allows an attacker to execute arbitrary code. Malicious code installation requires an access to the computer. By placing a specific DLL/OCX file, an attacker is able to force the process to load arbitrary DLL and execute arbitrary code in the context of the process. |
| A DLL Hijacking vulnerability in the programming software in Schneider Electric's SoMachine HVAC v2.1.0 allows a remote attacker to execute arbitrary code on the targeted system. The vulnerability exists due to the improper loading of a DLL. |
| A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges. |
| A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files. |
| An Improper XML Parser Configuration issue was discovered in Schneider Electric Wonderware Historian Client 2014 R2 SP1 and prior. An improperly restricted XML parser (with improper restriction of XML external entity reference, or XXE) may allow an attacker to enter malicious input through the application which could cause a denial of service or disclose file contents from a server or connected network. |
| An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack. |
| A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. |
| A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server. |
| A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack. |
| An issue was discovered in Schneider Electric Conext ComBox, model 865-1058, all firmware versions prior to V3.03 BN 830. A series of rapid requests to the device may cause it to reboot. |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to specify Arbitrary Server Target Nodes in connection requests to the Secure Gateway and Server components. |
| An Uncontrolled Resource Consumption issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The uncontrolled resource consumption vulnerability could allow an attacker to exhaust the memory resources of the machine, causing a denial of service. |
| A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0. |
| A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the web service contains a hidden system account with a hardcoded password. An attacker can use this information to log into the system with high-privilege credentials. |
| ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. |